Section: R500.E153CBulletin: E153-CDate: 5-10-09Supersedes: E153-A-116633 Foltz Parkway, Strongsville, OH 44149 USATelephone: (440) 572-1500 Fax
10Wiring instructions for the Clark • Reliance GL53 Illuminators (for 'C' and 'S' Series Gages).Note: Make sure that the power is
11Wiring instructions for the Standard and Vertical Clark • Reliance Flat Glass Gage Illuminators Note: Make sure that the power is turned off to the
12
13Confirm that the correct supply voltage is being applied to the illuminator power supply. The unit has been manufactured for a specific power source
14RECOMMENDED SPARE PARTS1 per sectionRepair Kit (incl. Glass & Gaskets)RK-35EC9 or S91 per sectionRepair Kit (incl. Glass & Gaskets)RK-35DC8
15*** REPLACEMENT PARTS WARNING ***The use of non-Original Equipment Manufacturer parts (such as glass, gaskets, probes, modules, etc.) will void th
16633 Foltz Parkway Strongsville, OH 44149 USAPhone (440) 572-1500 Fax (440) 238-8828 [email protected] www.clark-reliance.comcla
2Unpacking and inspectionUpon receipt of the Boiler Drum Level instruments, examine the contents of the container(s) for damage. Report any faulty con
3Boil-out Gage Practice and Policy On new boiler installations, it is common procedure to initially operate the boiler at a reduced pressure for a sho
4Recommended Blow-Down Procedure for Water Columns and Gage GlassesThe importance of proper cleaning and maintenance of the water column and the water
53. Always notify control room personnel prior to conducting a Blow-Down to prevent any false alarms or false trips.Recommended Maintenance and Annual
6Prismatic and Flat Glass GagesBEFORE YOU INSTALL THE GAGE GLASS:- Support brackets should be considered for gages over four feet long and weighing in
7Disassembly:-After pressure is relieved from the gage glass, remove from the boiler drum and lay flat on a workbench-Loosen end bolting first, workin
8Recommendations and Instructions for Hot Torquing Gage Glasses and Probe Type DevicesWhen a new piece of equipment, whether a Gage Glass or a Probe*
9Installation Instructions for Model GL-53 Water Gage Illuminators forTubular Glass Gages or Prismatic Gages1. General InformationModel GL-53 Water Ga